Cable Size Calculator
Ensure your electrical circuits are safe and efficient.
Cable Requirement
Sizing for Safety: UK Wiring Regulations
Beyond Amperage
Sizing a cable is more than just making sure it can carry the current. You must also ensure that the **voltage drop** remains within acceptable limits and that the cable can safely dissipate its own heat.
Our **cable size calculator** focuses on the critical 'voltage drop' calculation, which is the primary reason cables are oversized for long runs in UK domestic projects.
Permissible Drops (230V)
Thermal Derating
One of the biggest mistakes in DIY electrical work is ignoring **derating factors**. If a cable is run through a ceiling full of 300mm of rockwool insulation, its ability to carry current is reduced by **50%**.
This is why an electric shower (which uses 40-45 Amps) usually requires a massive **10.0mm²** cable, even though the same current could technically be carried by a 4.0mm² cable in open air.
mV/A/m Data
Electrical engineers use 'milliVolts per Amp per Metre' to calculate drop. For example, 2.5mm² cable has a rating of 18 mV/A/m. If you pull 20A through 10m of it, you lose 3.6V (20 x 10 x 18 / 1000).
Zs Impedance
Aside from voltage drop, cables must be sized to ensure the **Earth Loop Impedance (Zs)** is low enough to trip the circuit breaker within 0.4 seconds during a fault. This is why testing with a calibrated meter is essential.
Pro Tip: Cooker Circuits
For a standard modern electric oven and hob, always aim to install a **6.0mm²** cable on a **32A or 40A** breaker. Even if the current oven is smaller, installing a larger cable now makes the circuit 'future-proof' for high-power induction hobs.
Wiring & Cable FAQ
Electrical Safety Disclaimer
This calculator is for estimation only. Correct cable sizing depends on complex factors including grouping, ambient temperature, and earth fault protection. All electrical work in the UK must be certified by a registered electrician to comply with Part P of the Building Regulations.